OTPulse

Hitachi Energy Gateway Station

Plan Patch7.5ICS-CERT ICSA-23-059-02Mar 6, 2023
Attack VectorNetwork
Auth RequiredNone
ComplexityLow
User InteractionNone needed
Summary

Hitachi Energy Gateway Station versions 3.0.0.0 through 3.2.0.0 contain input validation (CWE-20) and buffer handling (CWE-120) flaws that allow remote attackers to cause service crashes, prevent the application from starting, or execute arbitrary scripts without authentication. Successful exploitation disrupts Gateway Station operation, which manages critical energy system communications and monitoring. The vulnerabilities are remotely exploitable with low attack complexity.

What this means
What could happen
An attacker could remotely cause parts of the Gateway Station to fail to start, execute unauthorized scripts on the device, or crash the service entirely, disrupting critical energy management operations.
Who's at risk
Energy utilities and power system operators who use Hitachi Energy Gateway Station for grid management and monitoring. This affects anyone managing distributed energy resources, substations, or SCADA integration points that rely on this gateway appliance.
How it could be exploited
An attacker on the network can send a crafted request to the Gateway Station service. Because the device does not properly validate input (CWE-20) and has buffer handling issues (CWE-120), the malformed input triggers a crash, service failure, or script execution without any credentials needed.
Prerequisites
  • Network access to the Gateway Station service port
  • No authentication required
  • No special configuration required
remotely exploitableno authentication requiredlow complexityaffects energy infrastructureno patch available for 3.0.0.0–3.2.0.0
Exploitability
Low exploit probability (EPSS 0.4%)
Affected products (3)
3 with fix
ProductAffected VersionsFix Status
Gateway Station (GWS): 3.0.0.03.0.0.03.3.0.0
Gateway Station (GWS): 3.1.0.03.1.0.03.3.0.0
Gateway Station (GWS): 3.2.0.03.2.0.03.3.0.0
Remediation & Mitigation
0/8
Do now
0/1
WORKAROUNDConfigure firewalls to restrict network access to the Gateway Station, allowing only trusted sources to connect to its service ports
Schedule — requires maintenance window
0/1

Patching may require device reboot — plan for process interruption

HOTFIXUpdate Hitachi Energy Gateway Station to version 3.3.0.0 or later
Long-term hardening
0/6
HARDENINGAvoid directly connecting the Gateway Station to the internet; use network segmentation to isolate it from untrusted networks
HARDENINGSeparate process control networks from other networks using a firewall with minimal exposed ports
HARDENINGPhysically secure the Gateway Station hardware from unauthorized access
HARDENINGDo not use the Gateway Station for internet browsing, email, or instant messaging
HARDENINGScan portable computers and removable media for malware before connecting to the control system network
HARDENINGEnforce strong password policies and access controls