Schneider Electric SCADAPack x70 Products
Schneider Electric SCADAPack x70 Remote Terminal Units contain a vulnerability in the Secure Lock access control feature that could allow unauthorized access to RTU configuration. The vulnerability affects the SCADAPack 47x, 47xi, 47xd, 470R, 57x, 3xx, and 32 product lines. Secure Lock is legacy functionality; Schneider Electric recommends migration to the Role-Based Access Control (RBAC) feature for access management. No vendor security updates are available; mitigation relies on proper configuration and network controls.
- Network access to the RTU on the same network or routable segment
- RTU must be configured with Secure Lock enabled (legacy configuration)
- User interaction may be required depending on the specific attack method
Patching may require device reboot — plan for process interruption
/api/v1/advisories/611897d7-7cfb-498b-b7c8-7292ce02e50cGet OTPulse briefings by email