Schneider Electric Modicon M340 Controller and Communication Modules
Schneider Electric Modicon M340 controller and associated communication modules contain an input validation vulnerability (CWE-20) in their network processing. A remote attacker can send malformed packets that cause the device to crash or become unresponsive, resulting in denial of service. Affected modules include the Ethernet/Serial RTU module, Modbus/TCP Ethernet modules, EtherNet/IP modules, and M580 Global Data modules. The vulnerability can be exploited via network access without authentication.
- Network access to the Modicon M340 controller or communication module on ports 21 (FTP) or Modbus/TCP port 502
- Device must be running an affected firmware version
Patching may require device reboot — plan for process interruption
/api/v1/advisories/a2651e31-ce35-4560-b04e-fbd9d6d29c52Get OTPulse briefings by email
Advisory breakdowns and incident analyses for the people actually defending OT environments. Sent when there's something worth your attention, not on a schedule. Free, no account required.