Authentication Bypass Vulnerability in Energy Services Using Elspec G5DFR
Monitor6.8SSA-734261Dec 9, 2025
Attack VectorPhysical
Auth RequiredNone
ComplexityLow
User InteractionNone needed
Summary
Siemens Energy Services solutions using Elspec G5 devices contain an authentication bypass vulnerability. A person with physical access to the device can reset the Admin password by inserting a USB drive containing a publicly documented reset string into the device's USB port, gaining full administrative control.
What this means
What could happen
An attacker with physical access to an Elspec G5DFR device can reset the administrator password using a USB drive, gaining full control of the device and potentially altering power quality monitoring, alarming, or data logging functions critical to grid operations.
Who's at risk
Energy utilities and power quality monitoring operations using Siemens Energy Services with Elspec G5DFR power quality analyzers and monitoring devices should assess exposure. The vulnerability affects facilities relying on G5DFR for grid monitoring, load analysis, and alarm generation in substations and distribution control centers.
How it could be exploited
An attacker physically approaches the Elspec G5DFR device, inserts a USB drive containing a publicly documented reset string, and executes the password reset procedure. Once the admin password is reset, the attacker gains administrative access to configure or disable monitoring and alarming functions on the device.
Prerequisites
- Physical access to the Elspec G5DFR device
- USB drive with publicly documented reset string
- Knowledge of the password reset procedure
physical access requireddefault or documented reset procedureaffects monitoring and control devicehigh impact on availability and integrity
Exploitability
Low exploit probability (EPSS 0.0%)
Affected products (1)
ProductAffected VersionsFix Status
Energy ServicesAll versionsNo fix yet
Remediation & Mitigation
0/3
Do now
0/2HARDENINGRestrict physical access to the Elspec G5DFR device with locked enclosures or controlled facility access
WORKAROUNDDisable USB ports on the device if the function is not required for operations
Schedule — requires maintenance window
0/1Patching may require device reboot — plan for process interruption
HOTFIXUpdate Elspec G5DFR firmware to version 1.2.3.13 or later
CVEs (1)